Tripp Lite PDUMH32HVATNET 7.7kW Single-Phase Switched Automatic Transfer Switch PDU, Two 200-240V IEC309 32A Blue Inputs, 16-C13 2-C19 Outlets, 2U, TAA

  • PDUMH32HVATNET Tripp Lite, Westborne Distribution Ltd
View Large Image

Product Code : PDUMH32HVATNET

Stock : Call for availability

Buying Information

Buy Price : £1,209.47

(£1,451.36 Inc. VAT)
  • Single-phase IEC309 200-240V 32A Blue (2P+E) input
  • 16 C13 and 2 C19 230V switched outlets in 2 breakered load banks
  • Automatic transfer switching within 1–5 ms
  • Ethernet network interface for remote access
  • Digital LED display for real-time status and current monitoring

The PDUMH32HVATNET 7.7kW Single-Phase 200-240V Switched Automatic Transfer Switch / ATS PDU provides remote power monitoring and enables redundant power for network devices with non-redundant power supply configurations. Ideal for data centers and server rooms, it mounts in 2U of space in EIA-standard racks and features 18 switched outlets (16 C13 and two C19) in two load banks, each bank protected by a 20A circuit breaker.Dual 3-meter input cords with IEC309 32A Blue (2P+E) plugs connect to separate primary and secondary single-phase 230V power sources. The PDU constantly evaluates the power quality of both input sources. Dynamic solid-state (TRIAC) automatic transfer switching allows the PDU to switch to the secondary source within 1–5 milliseconds should the primary source fail or become unstable to ensure your connected equipment operates without interruption.Built-in LX Platform network management interface. The Java-free LX Platform HTML5-based network interface enables full remote access for PDU status monitoring and email notifications via secure web browser, SNMP, telnet or SSH. It supports 10/100 Mbps auto-sensing for optimum communication with an Ethernet network. Optional EnviroSense2 modules (sold separate) provide a variety of environmental monitoring capabilities. Protocols supported include HTTP, HTTPS, SMTP, SNMPv1, SNMPv2, SNMPv3, telnet, SSH, FTP, DHCP and NTP. Primary and Secondary Inputs for Power Redundancy Provides remote power monitoring and enables redundant power for network devices single-corded and other non-redundant power suppl
y configurationsDual 3m input cords with IEC309 32A Blue (2P+E) plugs connect to separate primary and secondary single-phase power sources Automatic Transfer Switching Dynamic solid-state (TRIAC) automatic transfer switchingSwitches to secondary power source if primary source fails or becomes unstable1–5 ms transfer time ensures uninterrupted operation of connected equipmentBuilt-in processor monitors both sources and prevents switching if secondary source is unavailable or of lower quality than primary source Multifunction Digital LED Display Reports source A and source B input power status and other information, including power availability, line voltage, frequency, amps, kilowatts and power factor Advanced LX Platform Interface LX Platform interface allows full remote access for power monitoring with email notifications via secure web browser, SNMP, telnet or SSHReal-time load/current data with billing-grade accuracy (+/- 1 percent)Automated alerts help prevent accidental overloads, power loss and downtimeOptional EnviroSense2 modules (sold separately) provide a variety of environmental monitoring capabilities Broad Communications Compatibility Protocols supported include HTTP, HTTPS, SMTP, SNMPv1, SNMPv2, SNMPv3, telnet, SSH, FTP, DHCP and NTP Breaker Protected Output Load Banks Protect each of 2 single-phase output banksFront-panel LED indicates when breaker has tripped Cord Retention Sleeves Set of Plug-lock output power cable retention sleeves prevent accidental disconnection of connected devices Mounts Horizontally in 2U of Rack Space Compatible with EIA-standard 19 in. 4-post racks and rack enclosures TAA-Compliant Compliant with the Federal Trade Agreements Act (TAA) for GSA Schedule purchases

Alternate Codes : TLPDU0046, 10176484, 7413588, CE98423, 10469519
Additional product infomation

Westborne Distribution Ltd, PDUMH32HVATNET, Tripp Lite PDUMH32HVATNET 7.7kW Single-Phase Switched Automatic Transfer Switch PDU Two 200-240V IEC309 32A

cxCommerce powered by commerceXchange
The content of this site is based on sources we consider reliable, but for which we can't guarantee the accuracy, integrity or quality. The information displayed (e.g. specifications, prices, etc) should be considered as an indication only and may be changed at any time without prior notice, if you have any questions please call or email before purchase.
Product images are for illustrations only.